Revision March 2008, Doc. Name: 2007PDD23000011 
 
 
5-1
 
Chapter 5  Trial Run and Tuning Procedure 
This chapter, which is divided into two parts, describes trial run for servo drive and motor. One part is to 
introduce the trial run without load, and the other part is to introduce trial run with load. Ensure to complete 
the trial run without load first before performing the trial run with load. 
5.1 Inspection 
without 
Load 
In order to prevent accidents and avoid damaging the servo drive and mechanical system, the trial run 
should be performed under no load condition (no load connected, including disconnecting all couplings and 
belts). Do not run servo motor while it is connected to load or mechanical system because the unassembled 
parts on motor shaft may easily disassemble during running and it may damage mechanical system or even 
result in personnel injury. After removing the load or mechanical system from the servo motor, if the servo 
motor can runs normally following up the normal operation procedure (when trial run without load is 
completed), then the users can connect to the load and mechanical system to run the servo motor. 
 
 
¾
  In order to prevent accidents, the initial trial run for servo motor should be conducted under no load conditions 
(separate the motor from its couplings and belts). 
¾
  Caution: Please perform trial run without load first and then perform trial run with load connected. After the 
servo motor is running normally and regularly without load, then run servo motor with load connected. Ensure 
to perform trial run in this order to prevent unnecessary danger. 
After power in connected to AC servo drive, the charge LED will light and it indicates that AC servo drive is 
ready. Please check the followings before trial run: 
Item 
Content 
Inspection before 
operation 
(Control power is not 
applied) 
z
  Inspect the servo drive and servo motor to insure they were not damaged. 
z
  To avoid an electric shock, be sure to connect the ground terminal of servo drive to 
the ground terminal of control panel.  
z
  Before making any connection, wait 10 minutes for capacitors to discharge after 
the power is disconnected, alternatively, use an appropriate discharge device to 
discharge. 
z
  Ensure that all wiring terminals are correctly insulated. 
z
  Ensure that all wiring is correct or damage and or malfunction may result. 
z
  Visually check to ensure that there are not any unused screws, metal strips, or any 
conductive or inflammable materials inside the drive. 
z
  Never put inflammable objects on servo drive or close to the external regenerative 
resistor. 
z
  Make sure control switch is OFF. 
z
  If the electromagnetic brake is being used, ensure that it is correctly wired. 
z
  If required, use an appropriate electrical filter to eliminate noise to the servo drive.
z
  Ensure that the external applied voltage to the drive is correct and matched to the 
controller.