Chapter 6 Fault Code Information and Maintenance|                      
Revision August 2008, 03VE, SW V2.04 
6-7
6.2 Maintenance and Inspections 
Modern AC motor drives are based on solid state electronics technology. Preventive maintenance is 
required to operate this AC motor drive in its optimal condition, and to ensure a long life. It is 
recommended to have a check-up of the AC motor drive performed by a qualified technician. 
 
Daily Inspection: 
Basic check-up items to detect if there were any abnormalities during operation are: 
 
1. 
Whether the motors are operating as expected. 
2. 
Whether the installation environment is abnormal. 
3. 
Whether the cooling system is operating as expected. 
4. 
Whether any irregular vibration or sound occurred during operation. 
5. 
Whether the motors are overheating during operation. 
6. 
Always check the input voltage of the AC drive with a Voltmeter. 
 
Periodic Inspection:
 
Before the check-up, always turn off the AC input power and remove the cover. Wait at least 10 
minutes after all display lamps have gone out, and then confirm that the capacitors have fully 
discharged by measuring the voltage between +1/+2 and -. The voltage between +1/+2 and-should 
be less than 25VDC. 
 
DANGER!
 
1. Disconnect 
AC 
power before processing! 
2. 
Only qualified personnel can install, wire and maintain AC motor drives. Please take off any 
metal objects, such as watches and rings, before operation. And only insulated tools are 
allowed. 
3. 
Never reassemble internal components or wiring. 
4. 
Prevent static electricity.