Appendix B  Accessories|                      
Revision August 2008, 03VE, SW V2.04 
B-15
B.5 Zero Phase Reactor (RF220X00A)  
  
  
   
Recommended Wire 
Size 
Cable 
type 
(Note)   AWG mm
2
 
Nominal 
(mm
2
Qty.
Wiring 
Method
10  ≦5.3 
5.5 
Diagram 
Single-
core 
2  ≦33.6  ≦38 
Diagram 
12  ≦3.3 
3.5 
Diagram 
Three-
core 
1  ≦42.4  ≦50 
Diagram 
Note: 600V Insulated unshielded Cable. 
 
 
 
 
Power
Supply
Zero Phase Reactor
MOTOR
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
 
 
 
 
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Power
Supply
Zero Phase Reactor
MOTOR
 
Note 1: The table above gives approximate 
wire size for the zero phase reactors but the 
selection is ultimately governed by the type 
and diameter of cable fitted i.e. the cable 
must fit through the center hole of zero 
phase reactors. 
 
 
Note 2: Only the phase conductors should 
pass through, not the earth core or screen. 
 
 
Note 3: When long motor output cables are 
used an output zero phase reactor may be 
required to reduce radiated emissions from 
the cable.
Diagram B 
Please put all wires through 4 cores in 
series without winding. 
Diagram A
 
Please wind each wire 4 times around the 
core. The reactor must be put at inverter 
output as close as possible. 
 
Dimensions are in millimeter and (inch)