Appendix B  Accessories
B-40 
Revision August 2008, 03VE, SW V2.04
 
B.10 Multi-function I/O Extension Card
 
B.10.1 Functions 
EMV-APP01 optional multi-function I/O extension card is exclusively designed for VFD-VE 
series and used with firmware version 2.04 and above. It communicates with the AC motor 
drive by RS-485 communication port (COM1). To make sure that the communication is 
normal, it needs to set the COM1 communication protocol to RTU mode (8, N, 1), i.e. set 
Pr.09-04 to 12 no matter what the baud rate switch is set. 
 
RS485 port
High/Low baud  rate switch
Communi cation
indicator
Power indi cator
Analog s ignal common
Output power
Multi-function 
input terminals
Analog output 
terminals
Multi-function 
output ter minals
Multi-function
output common terminal
 
 
NOTE
 
Please operate by the following steps for switching the high/low baud rate,  
1. make sure that RS-485 cable is disconnected before operation 
2. switch the high/low baud rate 
3. set Pr.09-01 to the corresponding baud rate to finish setting 
If the RS-485 cable is connected before changing the high/low baud rate, the 
communication function will still be invalid even if the communication baud rate (Pr.09-01) is 
changed to the corresponding baud rate and the ERROR indicator is normal. 
 
Terminals 
Description 
POWER 
Power indicator. It will be ON when EMV-APP01 connects to the AC motor drive 
correctly. 
ERROR 
ERROR indicator. It will be ON when EMV-APP01 can communicate with the AC 
motor drive or it will blink. 
HIGH/LOW 
Baud rate switch for extension card: 
HIGH: set the baud rate to 115200 
LOW: set the baud rate to 9600