Chapter 8: Managing External Devices 
 
162
 
 
 
EMX and PX2 PDU Cascading Connections 
Up to four (4) devices are supported as part of a daisy chain. 
Specifically, a EMX can have up to three (3) additional EMXs connected 
to it, or up to three (3) PX2 devices connected to it.  
Note: For help on setting up and configuring PX2 devices, see the PX2 
Help
 for additional information. 
The following configurations are supported: 
 
EMX  
 EMX 
 EMX 
 EMX 
 
EMX 
 PX2 
 PX2 
 PX2 
The first EMX is the master device, and all devices connected to the 
master are its slaves. The master device is device 1 in the chain, and all 
subsequent devices are numbered sequentially.  
The first slave device connects to the USB-A port on the EMX master 
device from the slave's USB-B port via a USB cable. If another device is 
added to the chain, connect the new device's USB-B port to the existing 
devices USB-A port using a USB cable.  
All EMX devices must be using the EMX 2.2 (or later) firmware, and all 
PX2 devices must be using PX-2.3 (or later) firmware. If the devices are 
not running the supported firmware, upgrade your device before you 
connect each device in the chain.  
All devices in the chain are accessible over an IP network, with the 
master EMX acting as a network bridge. The USB-cascading 
configuration only supports wired networking so you must make sure: 
 
The master device has "wired" Ethernet connectivity. 
 
None of the slave devices has wired Ethernet connectivity. Even 
though you connect any slave device to the LAN through a network 
cable, its wired Ethernet interface is automatically disabled. 
 
None of the devices in the chain has wireless connectivity. 
The devices in the chain are displayed in the explorer pane on the left 
once they are connected and detected by the master EMX. Clicking on 
the master EMX displays all available ports in the data pane.