Справочник Пользователя для Mitsubishi Electronics Q64TCTTBWN

Скачать
Страница из 430
189
CHAPTER 4 FUNCTIONS
4
4.8  D
erivative Action Selection F
unction
  
4.8
Derivative Action Selection Function
An derivative action appropriate for each of fixed value action and ramp action can be selected and the action 
characteristic can be improved using this function.
(1) Action
Each type of derivative action operates as shown below.
(2) Setting method
Set a value in CH Derivative action selection ((Un\G729, Un\G745, Un\G761, Un\G777).
For details on the setting, refer to the following.
CH Derivative 
action selection 
(Un\G729, Un\G745, 
Un\G761, Un\G777)
Action
Measured value 
derivation (0)
This setting effectively 
prevents the 
temperature from being 
affected by disturbance, 
though the performance 
to follow the set value 
can be low.
Deviation derivation (1)
This setting allows the 
temperature to follow 
the set value well, 
though the disturbance 
effect is great.
Common
Ramp action
Fixed value action
Disturbance
Set value (SV)
Temperature 
process value 
(PV)
Temperature
process value
(PV)
Set value (SV)
Disturbance
Fixed value action
Ramp action