CHAPTER 4 FUNCTIONS
4
4.24  Pr
oportional Band Setting Fu
nction
  
4.24
Proportional Band Setting Function
Proportional band (P) values can be set for heating and cooling separately using this function. Different gradients can 
be set by using different proportional band (P) values in a heating and cooling area.
(1) Setting method
(a) For heating
Set the value in CH Heating proportional band (Ph) setting (Un\G35, Un\G67, Un\G99, Un\G131). 
(
(b) For cooling
Set the value in CH Cooling proportional band (Pc) setting (Un\G720, Un\G736, Un\G752, Un\G768). 
(
Heating-cooling
Manipulated value 
for cooling (MVc) 100%
Manipulated value 
for heating (MVh) 0%
Manipulated value 
for heating (MVh) 100%
Manipulated value 
for cooling (MVc) 0%
100%
0%
Set value (SV)
Heating proportional 
band (Ph)
Cooling
Heating
Cooling proportional 
band (Pc)
-100%
Only cooling 
proportional band (Pc) 
can be narrowed.
Manipulated value 
for heating (MVh)
Manipulated value 
for cooling (MVc)