5.4.3
Heater disconnection detection wiring and setting example 
for three-phase heater
The following figure shows a wiring and setting example to detect a three-phase heater disconnection by using the 
heater disconnection detection function.
Three-phase heater disconnection detection is executed by measuring the currents of two of the three cables.
In the above wiring example, set CT CT input channel assignment setting (Un\G264 to Un\G271) as indicated below.
CT input
Buffer memory address
Set value
CT1
Un\G264
1
CT2
Un\G265
1
CT3
Un\G266
2
CT4
Un\G267
2
CT5
Un\G268
3
CT6
Un\G269
4
CT7
Un\G270
0
CT8
Un\G271
0
Q64TCTTBWN
Q64TCRTBWN
L1
L2
L3
L4
COM-
CH1
CH2
CH3
CH4
CT1
CT2
CT1
CT2
CT3
CT3
CT4
CT4
CT5
CT5
CT6
CT6
CT7
CT7
CT8
CT8
To three-phase heater (used in CH2 loop)
To single-phase heater (used in CH3 loop)
To single-phase heater (used in CH4 loop)
Unused
Controlled 
object