Справочник Пользователя для Mitsubishi Electronics Q64TCTTBWN

Скачать
Страница из 430
367
CHAPTER 8 TROUBLESHOOTING
8
8.6  Er
ror C
ode List
  
8.6
Error Code List
When an error occurs in the Q64TCN during data write to the CPU module or data read from the CPU module, one of 
the following error codes is stored in Write data error code (Un\G0).
In addition, the error occurred is notified to the CPU module.
Error code
(hexadecimal)
Cause
Operation at error occurrence
Action
0001
H
Hardware error
The operation varies depending on 
the symptom.
• Check that the terminal block or the 
cold junction temperature 
compensation resistor is not 
disconnected or loose.
• Replace the Q64TCN.
• Please consult your local Mitsubishi 
representative.

2
H
*1
Data
 
(other than 0) is being written to 
the system area
*2
.
• The data written is retained.
• When data is written to multiple 
system areas, the address with the 
smallest number of the buffer 
memory area where an error was 
detected is stored.
*5
• Return the value to 0 and turn off, 
on, and off Error reset instruction 
(Yn2).
• Delete the program that is writing 
data to the system area.

3
H
*1
Data is being written in the operation 
mode
*4 
to the area where data can be 
written only in the setting mode
*3
.
• The data written is retained.
• When data is written to multiple 
system areas, the address with the 
smallest number of the buffer 
memory area where an error was 
detected is stored.
*5
• Follow the instructions below for 
error reset.
1. Change the mode to the setting 
mode.
2. Set the correct value and turn off, 
on, and off Setting change 
instruction (YnB).
3. Turn off, on, and off Error reset 
instruction (Yn2).
• If switching from the operation mode 
to the setting mode, check that PID 
continuation flag (Un\G169) is set to 
Stop (0), and turn on and off 
Setting/operation mode instruction 
(Yn1).

4
H
*1
Data outside the settable range is 
being written.
• The data written is retained.
• If temperature, time, or percentage 
settings exceed upper limit 
value/lower limit value, change the 
data within those values.
• When data is written to multiple 
system areas, the address with the 
smallest number of the buffer 
memory area where an error was 
detected is stored.
*5
Set data within the range.