(1) Stopping operation
If PID continuation flag (Un\G169) is set to Continue (1), control does not stop even when Setting/operation mode instruction 
(Yn1) is turned off. Change PID continuation flag (Un\G169) to Stop (0) and turn off Setting/operation mode instruction 
(Yn1).
Whether the control has been stopped can be checked by Setting/operation mode status (Xn1) being off.
1.
Open the "Device/Buffer Memory Batch Monitor" 
window.
[Online] 
 [Monitor] 
 [Device/Buffer Memory 
Batch]
2.
In "Device Name", enter and display the name of the 
CPU module device to be refreshed in the Q64TCN.
3.
Select the following output signals and click 
.
Turn off the output signals in the CPU module to 
turn off the following output signals in the Q64TCN.
• Setting/operation mode instruction (Yn1)
• E
2
PROM backup instruction (Yn8)
• Default setting registration instruction (Yn9)
• Setting change instruction (YnB)
This operation stops the operation of the Q64TCN.