10 - 32                                                                                                                                                      10 - 32
MELSEC-Q
10 TROUBLESHOOTING
10.3.4 Troubleshooting when an external device transmitted a message and "RD" LED
blinked, but the Read Request signal was not turned ON
Symptom
Cause
Corrective action
MC
Bidi
rectio
na
No
n
procedure
•  Communication protocol
is set incorrect.
•  
Check if the communication protocol is set correctly.
•  
Check if the mode was switched without using the
buffer memory mode switching area.
Note
•  
The communication protocol setting contents and
the communication protocol in the current operation
can be checked at buffer memory addresses 250
H
to (CH1) and 260
H
 (CH2).
•  When "Check CD
terminal" was set, the CD
terminal was turned off.
•  
Since messages are skipped when the CD terminal is
turned OFF when "Check CD terminal" is set, change
the wiring so that the CD terminal remains on all the
time.
•  When DC control is
selected, the necessary
DC codes are not
transmitted.
•  Check if a message is transmitted without transmitting
"DC1 (11
H
)" after the external device transmits "DC3
(13
H
)" during DC1/DC3 external control.
•  Check if the next message is transmitted without
adding "DC2 (12
H
)" after the external device transmits
"DC4 (14
H
)" during DC2/DC4 external control.
•  The end code was not
received, or fixed length
data was not received.
•  
Check if the end code set at the Q series C24 and the
end code transmitted from the external device are the
same.
•  
Check if the external device transmitted the fixed
length designated at the Q series C24.
•  
Check if the trailer frame was transmitted during
communications by user frame.
Note
•  
When the send data from the external device is
correct, take the corrective action described in
Sections 10.3.10 and 10.3.11.
•  The Q series C24
setting and message
format do not match.
•  The data count basics, message format, etc. depend
on the following settings.
  ASCII-BIN conversion enable/disable
  Transparent code setting
  User frame setting
See the relevant section for a description of operation
according to the set contents and setting of each item.
•  An external device
transmitted a message
and "RD" blinked, but
the read request signal
(X0) was not turned
ON.
•  The Q series C24 data
communications
monitoring time is set to
"infinite", or the
monitoring time is too
long.
•  
Set, or shorten, the monitoring time and retransmit the
message from the external device and determine the
trouble from the contents of the time-out error.
Note
•  
Error detection by the watchdog timer (timer 0 to
timer 2) is possible in the following cases.
  When part of a message is skipped.
  When transmission from an external device is
interrupted.
See Chapter 6 of User's Manual (Application) for a
detailed description of the monitoring time.