The following shows the Q series C24 performance specifications.
See the User's Manual of the QCPU (Q mode) for general specifications.
3.1 Performance Specifications
The following shows the Q series C24 performance specifications. For the
transmission specifications when communicating via the modem function, see this
section and Chapter 3 of User's Manual (Application).
(1)   Transmission specification
Specifications
Item
QJ71C24N
QJ71C24
QJ71C24N-R2
QJ71C24-R2
QJ71C24N-R4
CH1
RS-232-compliance
(D-sub 9 pin)
RS-232-compliance
(D-sub 9 pin)
RS-422/485-compliance
(2-piece plug-in connector socket
block)
Interface
CH2
RS-422/485-compliance
(2-piece terminal block)
RS-232-compliance
(D-sub 9 pin)
RS-422/485-compliance
(2-piece plug-in connector socket
block)
Line
Full-duplex/half-duplex communications
MC protocols
communication
Half-duplex communications
Non procedure protocol
communication
Full-duplex/full-duplex communications
Communications
system (
1)
Bidirectional protocol
communication
Full-duplex/full-duplex communications
Synchronization method
Start-stop synchronization method
[QJ71C24N(-R2/R4)]
50
300
600
1200
2400
4800
9600
14400
19200
28800
38400
57600
115200
230400
(bps)
 Transmission speed 230400 bps is available for only CH1.  (Not available for CH2)
 Total transmission speed of two interfaces is available up to 230400 bps.
 Total transmission speed of two interfaces is available up to 115200 bps when the communication data
monitoring function is used.
[QJ71C24(-R2)]
50
300
600
1200
2400
4800
9600
14400
19200
28800
38400
57600
115200
-
(bps)
Transmission speed
 Total transmission speed of two interfaces is available up to 115200 bps.
Start bits
1
Data bits
7/8
Parity bits
1 (vertical parity) or none
Data format
Stop bits
1/2
MC protocol communication
Processes one request during installed PLC CPU END processing.
 Number of scans that must be processed/number of link scans depends on the contents of the request.
(See Reference Manual.)
Access cycle
Non procedure protocol
communication
Bidirectional protocol
communication
Sends each time a send request is issued. Can receive at any time.
Parity check
All protocols and when ODD/EVEN is selected by parameter.
Error detection
Sum check code
MC protocol/bidirectional protocol selected by parameter.
Non procedure protocol selected by user frame.