Input Calibration 
136 
UDC2500 Universal Digital Controller Product Manual 
4/07 
5 Input 
Calibration 
 
WARNING—SHOCK HAZARD
  
INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND 
SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN 
ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION. 
5.1 Overview 
Introduction 
This section describes the field calibration procedures for Input 1 and Input 2. 
•  All input actuations in every UDC2500 controller are fully factory-calibrated and are 
ready for configuration by the user. 
•  Field Calibration can improve the accuracy of the Controller if necessary for a 
particular application. 
 
CAUTION 
The field calibration will be lost if a change in input type configuration is implemented at a later 
time. The original factory calibration data remains available for later use after a field calibration 
is done. See subsection 0 if you want to restore factory calibration values. 
 
What's in this section? 
The following topics are covered in this section. 
TOPIC 
See Page 
5.2  Minimum and Maximum Range Values 
5.3 Preliminary 
Information 
5.4  Input #1 Set Up Wiring 
5.5  Input #1 Calibration Procedure 
5.6  Input #2 Set Up Wiring 
5.7  Input #2 Calibration Procedure 
5.8  Restore Factory Calibration