Modbus Read, Write and Override Parameters plus Exception Codes 
4/07 
UDC2500 Universal Digital Controller Product Manual 
209 
10.7.8 Control 
Table 10-16  Set-up Group – Control 
Parameter 
Description 
Register 
Address 
Data 
Type 
Access 
Data Range or 
Enumerated Selection 
 
Hex 
Decimal 
 
 
 
Tuning 
Parameter 
Selection 
00AC 
172 
INT 
R/W 
0 = One set only 
1 =  2 sets keyboard selected 
2 =  2 sets with PV automatic 
switchover 
3 =  2 sets with setpoint (SP) 
automatic switchover 
Automatic 
Switchover 
Value (used with 
172 selection 2 
or 3) 
0038 
056 
FP 
R/W 
Within the PV Range in 
engineering units 
Local Setpoint 
Source (Number 
of LSPs) 
00AD 
173 
INT 
R/W 
0 = One Local Setpoint 
1 = Two Local Setpoints 
Power Up Mode 
Recall 
0082 130 
INT R/W   Control Setpoint 
 Mode  Mode 
0 = MAN 
LSP 
1 = AUTO 
LSP 
2 = AUTO 
Last RSP 
3 = LAST 
Last SP 
4 = LAST 
Last Local SP 
RSP Source 
0083 
131 
INT 
R/W 
0 = None 
1 = Input 2 
Setpoint 
Tracking 
008A 
138 
INT 
R/W 
0 = None 
1 = LSP = PV (when in 
Manual) 
2 = LSP = RSP (when 
switched) 
Control Setpoint 
High Limit 
0007 
007 
FP 
R/W 
0 to 100% of PV 
(engineering units) 
Control Setpoint 
Low Limit 
0008 
008 
FP 
R/W 
0 to 100% of PV 
(engineering units) 
Control Output 
Direction 
0087 
135 
INT 
R/W 
0 =  Direct  
1 =  Reverse