Справочник Пользователя для Honeywell UDC2500

Скачать
Страница из 243
Installation 
4/07 
UDC2500 Universal Digital Controller Product Manual 
31 
 
Configure:
A2S1TY = NONE 
A2S2TY = NONE 
2 Wire Transmitter 
_
 
+
 
INPUT 1
OUTPUT 3 
250 
Ω
26 +
27 -
5 + 
6 - 
If necessary, install a zener diode here to reduce voltage at the 
transmitter.  A 1N4733 will reduce the voltage at the transmitter to 
approximately 25 Vdc.
 
 
Figure 2-18  Transmitter Power for 4-20 mA — 2 wire Transmitter Using Open 
Collector Alarm 2 Output 
 
 
2 Wire Transmitter 
_
 
+
 
INPUT 1
AUXILIARY OUTPUT 
250 
Ω
26 +
27 -
12 + 
13 - 
Configure:
        AUXOUT = OUT 
Auxiliary Output Calibration 
        ZEROVAL = 4095 
        SPANVAL = 4095 
If necessary, install a zener diode here to reduce voltage at the 
transmitter.  A 1N4733 will reduce the voltage at the transmitter to 
approximately 25 Vdc.
 
 
 
Figure 2-19  Transmitter Power for 4-20 mA — 2 Wire Transmitter  
Using Auxiliary Output