4.10  Mo
ving Ave
raging Process to
 a Temper
ature
 P
rocess Value (PV)
  
4.10
Moving Averaging Process to a Temperature Process 
Value (PV)
Moving averaging process can be set to a temperature process value (PV). With this function, the fluctuation of 
temperature process values (PV) can be reduced in electrically noisy environments or in the environments where 
temperature process values (PV) fluctuate greatly. The moving averaging process can be disabled to hasten the 
response to the change of temperature process values (PV).
(1) Setting method
Configure the settings as below.
1.
Set Enable (0) to "Moving Averaging Process Setting" in the intelligent function module switch 
setting to use the moving averaging process.
Set Disable (1) to "Moving Averaging Process Setting" in the intelligent function module switch 
setting when not using the moving averaging process.
For details on the setting method, refer to the following.
2.
Set the number of moving averaging to CH Number of moving averaging (Un\G698 to Un\G701).
● When Disable (1) is set to "Moving Averaging Process Setting" in the intelligent function module switch setting, the set 
value in CH Number of moving averaging (Un\G698 to Un\G701) is ignored. When Enable (0) is set to "Moving 
Averaging Process Setting" in the intelligent function module switch setting, if the value out of the setting range is set to 
CH Number of moving averaging (Un\G698 to Un\G701), a write data error (error code: 4
H
) occurs.
● For the module, the moving averaging process is enabled and the number of moving averaging is 2 times as default. 
Change the settings if necessary.
Buffer memory 
area name
Buffer memory address
Setting range
Reference
CH1
CH2
CH3
CH4
Number of moving 
averaging
Un\G698
Un\G699
Un\G700
Un\G701
2 to 10 (times)
(Default value: 2)
Common