Справочник Пользователя для Mitsubishi Electronics Q64TCTTN

Скачать
Страница из 430
258
4.25
Cooling Method Setting Function
An auto tuning calculation formula is automatically selected according to the selected cooling method during auto 
tuning and the operation is started using this function.
Select one of the following characteristics:
 • Air cooled: The cooling characteristic is nonlinear and cooling ability is low.
 • Water cooled: The cooling characteristic is nonlinear and cooling ability is high.
 • Linear: The cooling characteristic is close to the linear shape.
PID constants are calculated and executed based on this setting during auto tuning; therefore, more appropriate PID 
constants can be found by setting more applicable cooling characteristic of a device.
For details on the auto tuning function, refer to the following.
(1) Setting method
Set the characteristic in Cooling method setting (Un\G719). (
● An auto tuning calculation formula to find PID constants is determined based on this setting; therefore, configure this 
setting before executing auto tuning.
● "Air Cooled" and "Water Cooled" roughly indicate the level of the cooling ability. When a device is too cooled even if it is 
set to air cooled, set the module to Water cooled (1
H
). When a device is not very cooled even if it is set to water cooled, 
set the module to Air cooled (0
H
).
● In general, the ability of water cooling is higher than that of air cooling and cooling may be too strong if the same PID 
constants as air cooling are used. Some time is required until the control becomes stable upon the initial start-up, 
disturbance, or setting change. Therefore, in auto tuning, PID constants for when the module is set to Water cooled (1
H
become larger than those for when the module is set to Air cooled (0
H
).
Heating-cooling
Cooling system and cooling characteristics
0
0.2
0.4
0.6
0.8
1
0
10
20
30
40
50
60
70
80
90
100
Manipulated value for cooling (MVc) (%)
Cooling characteristics (rate 
of when the manipulated value 
for cooling (MVc) 100% is 1)
Complete linear 
characteristics
Devices such as 
cooling fans
Devices such as 
electron coolers
Air-cooling
Devices such as 
cooling water piping
Water-cooling
Linear