Appendix 4.6
When a sequence program was used for the initial 
setting
(1) Stopping operation
● If PID continuation flag (Un\G169) is set to Continue (1), control does not stop even when Setting/operation mode 
instruction (Yn1) is turned off. Change PID continuation flag (Un\G169) to Stop (0) and turn off Setting/operation mode 
instruction (Yn1).
Whether the control has been stopped can be checked by Setting/operation mode status (Xn1) being off.
● If a CPU continuation error (such as SP.UNIT DOWN and UNIT VERIFY ERR.) is occurring due to an error in the module 
to be changed, the buffer memory data cannot be saved.
1.
Open the "Device test" window.
[Online]  
[Debug]  
[Device 
test...]
2.
Turn off the following output signals to stop the 
operation of the module.
• Setting/operation mode instruction (Yn1)
• E
2
PROM backup instruction (Yn8)
• Default setting registration instruction (Yn9)
• Setting change instruction (YnB)
3.
If the buffer memory data to be saved beforehand is 
not recorded, monitor the data in "Buffer memory 
batch monitor" and record it.
[Online] 
 [Monitor] 
 [Buffer memory batch...]