Справочник Пользователя для Siemens SIMATIC NET PROFIBUS

Скачать
Страница из 490
Passive Components for RS-485 Networks
4-35
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Technical Specifications
The following table shows the technical data of the various bus connectors:
Table 4-7
Technical Specifications of the IP 20-compliant Bus Connectors
Order numbers:
6ES7 972-
... 0BA11-0XA0
... 0BB11-0XA0
6ES7 972-
... 0BA40-0XA0
... 0BB40-0XA0
6ES7 972-
0BA30-0XA0
6GK1 500-
0EA02
PG socket
0BA11: no
0BB11: yes
0BA40: no
0BB40: yes
no
no
Max. transmission
rate
12 Mbps
12 Mbps
1.5 Mbps
12 Mbps
Terminating resistor
and disconnect
function
integrated
integrated
no
integrated
Cable outlet
vertical
oblique 35
_
oblique 30
_
axial
Interfaces
S
to PROFIBUS
node
S
to PROFIBUS
LAN cable
9-pin sub-D male
connector
4 modular
terminals for wires
up to 1.5 mm
2
9-pin sub-D male
connector
4 modular
terminals for wires
up to 1.5 mm
2
9-pin sub-D male
connector
4 insulation
displacement
terminals for wires
0.644 
"
 0.04 mm
9-pin sub-D male
connector
4 modular
terminals for wires
up to 1.5 mm
2
Connectable
PROFIBUS cable
diameter
"
 0.5 mm
"
 0.5 mm
"
 0.5 mm
"
 0.5 mm
Power supply (must
be supplied by DTE)
4.75 to 5.25 V DC
4.75 to 5.25 V DC
---
4.75 to 5.25 V DC
Current consumption
max. 5 mA
max. 5 mA
---
max. 5 mA
Permitted ambient
conditions
S
Operating
temperature
S
Transport/storage
temperature
S
Relative humidity
_
C to +60 
_
C
-25 
_
C to +80 
_
C
max. 75 % at
+25 
_
C
_
C to +60 
_
C
-25 
_
C to +80 
_
C
max. 75 % at
+25 
_
C
_
C to +60 
_
C
-25 
_
C to +80 
_
C
max. 75 % at
+25 
_
C
_
C to +55 
_
C
-25 
_
C to +70 
_
C
max. 95 % at
+25 
_
C
Dimensions (in mm)
15.8 
 
 54 
 
 34
16 
 
 54 
 
 38
15 
 
 58 
 
 34
15 
 
 39 
 
 57
Weight
approx. 40 g
approx. 40 g
approx. 30 g
approx. 100 g
Disconnect Function
The disconnect function means that the remaining LAN cable is disconnected from
the bus when the terminating resistor is activated. If the terminating resistor is
accidentally activated in the middle of the LAN cable, the error can be recognized
and localized immediately due to the nodes that are no longer accessible.