MELSEC-Q
 
5   DATA USED FOR POSITIONING CONTROL 
 
 Even when the PLC READY signal [Y0] is ON, the values or contents of the 
following can be changed: basic parameters 2, detailed parameters 2, positioning 
data, and block start data. 
 The servo parameter is transmitted from QD75MH to the servo amplifier when the 
initialized communication carried out after the power supply is turned ON or the PLC 
CPU is reset. 
The power supply is turned ON or the PLC CPU is reset after writing servo 
parameter in flash ROM of QD75MH if the servo parameter is transmitted to the 
servo amplifier. 
The following servo parameter in the buffer memory is transmitted to the servo 
amplifier when the PLC READY [Y0] turns from OFF to ON. 
• 
Pr.108
 Auto tuning mode  (Basic setting parameters) 
• 
Pr.109
 Auto tuning response  (Basic setting parameters) 
• 
Pr.122
 Feed forward gain  (Gain • filter setting parameters)  
• 
Pr.124
 Ratio of load inertia moment to servo motor inertia moment  (Gain • filter 
setting parameters) 
• 
Pr.125
 Model loop gain  (Gain • filter setting parameters) 
• 
Pr.126
 Position loop gain  (Gain • filter setting parameters) 
• 
Pr.127
 Speed loop gain  (Gain • filter setting parameters) 
• 
Pr.128
 Speed integral compensation  (Gain • filter setting parameters) 
• 
Pr.129
 Speed differential compensation  (Gain • filter setting parameters) 
 The only valid data assigned to these parameters are the data read at the moment 
when a positioning or JOG operation is started. Once the operation has started, any 
modification to the data is ignored. 
Exceptionally, however, modifications to the following are valid even when they are 
made during a positioning operation:  acceleration time 0 to 3, deceleration time 0 to 
3, and external start command. 
• Acceleration time 0 to 3 and deceleration time 0 to 3: 
Positioning data are pre-read and pre-analyzed. Modifications to the 
data four or more steps after the current step are valid. 
• External command function selection: The value at the time of detection is valid.