5 - 32 
MELSEC-Q
 
5   DATA USED FOR POSITIONING CONTROL 
 
1)  Generally, the OP is set at the lower limit or upper limit of the stroke limit. 
2)  By setting the upper limit value or lower limit value of the software stroke limit, 
overrun can be prevented in the software. However, an emergency stop limit 
switch must be installed nearby outside the range. 
To invalidate the software stroke limit, set the setting value to "upper limit 
value = lower limit value". (The setting value can be anything.) 
When the unit is "degree", the software stroke limit check is invalid during 
speed control (including speed-position switching control, position-speed 
switching control) or during manual control. 
 
Pr.14 Software stroke limit selection 
Set whether to apply the software stroke limit on the "current feed value" or the 
"machine feed value". The software stroke limit will be validated according to the 
set value. 
To invalidate the software stroke limit, set the setting value to "current feed value". 
 
Pr.15 Software stroke limit valid/invalid setting 
Set whether to validate the software stroke limit during JOG/Inching operation and 
manual pulse generator operation. 
 
Setting value, setting range 
Setting value buffer memory 
address 
Item 
Value set with peripheral device 
Value set with PLC program 
Default 
value 
Axis 1  Axis 2  Axis 3  Axis 4 
Pr.16
 
Command in-position width 
The setting value range differs depending on the "
Pr.1
 Unit 
setting". 
Here, the value within the [Table 1] range is set. 
 
 [Table 1] on right page
 
100 
24 
25 
174 
175 
324 
325 
474 
475 
Pr.17
 
Torque limit setting value 
1 to 1000 (%) 
1 to 1000 (%) 
300 
26 
176 
326 
476 
0 : WITH mode 
Pr.18
 
M code ON signal output 
timing 
1 : AFTER mode 
0 27 
177 
327 
477 
 
Pr.16 Command in-position width 
 
Set the remaining distance that turns the command in-position ON. The command 
in-position signal is used as a front-loading signal of the positioning complete 
signal. When positioning control is started, the "command in-position flag" (3rd flag 
from right) in "
Md.31
 Status" turns OFF, and the "command in-position flag" turns 
ON at the set position of the command in-position signal. 
 
ON
OFF
Pr.16
Command in-position width
Velocity
Position control start
Command
in-position flag