5 - 110 
MELSEC-Q
 
5   DATA USED FOR POSITIONING CONTROL 
 
Da.11 Shape 
 
Set whether to carry out only the local "block start data" and then end control, or to 
execute the "block start data" set in the next point. 
 
Setting value 
Setting details 
0 : End 
Execute the designated point's "block start data", and then complete the control. 
1 : Continue 
Execute the designated point's "block start data", and after completing control, execute the next 
point's "block start data". 
 
 
Da.12 Start data No. 
 
Set the "positioning data No." designated with the "block start data". 
 
 
Da.13 Special start instruction 
 
Set the "special start instruction " for using "high-level positioning control". (Set 
how to start the positioning data set in "
Da.12
Start data No.".) 
 
Setting value 
Setting details 
00
H
 :  Block start 
(Normal start) 
Execute the random block positioning data in the set order with one start. 
01
H
 :  Condition start 
Carry out the condition judgment set in "condition data" for the designated positioning data, and 
when the conditions are established, execute the "block start data". If not established, ignore 
that "block start data", and then execute the next point's "block start data". 
02
H
 :  Wait start 
Carry out the condition judgment set in "condition data" for the designated positioning data, and 
when the conditions are established, execute the "block start data". If not established, stop the 
control (wait) until the conditions are established. 
03
H
 :  Simultaneous 
start 
Simultaneous execute (output pulses at same timing) the positioning data with the No. 
designated for the axis designated in the "condition data".  
Up to four axes can start simultaneously. 
04
H
 :  Repeated start 
(FOR loop) 
Repeat the program from the block start data with the "FOR loop" to the block start data with 
"NEXT"  for the designated No. of times. 
05
H
 :  Repeated start 
(FOR condition) 
Repeat the program from the block start data with the "FOR condition" to the block start data 
with "NEXT" until the conditions set in the "condition data" are established. 
06
H
 :  NEXT start 
Set the end of the repetition when "05
H
: Repetition start (FOR loop)" or "06
H
: Repetition start 
(FOR condition)" is set. 
 
Refer to Chapter 10 "High-level Positioning Control" for details on the control. 
 
Da.14 Parameter 
 
Set the value as required for "
Da.13
Special start instruction ". 
 
Da.13
Special start instruction 
Setting value 
Setting details 
Block start (Normal start) 
– 
Not used. (There is no need to set.) 
Condition start 
Wait start 
Simultaneous start 
1 to 10 
Set the condition data No. (Data No. of 
"condition data" is set up for the 
condition judgment.) 
Repeated start (FOR loop) 
0 to 255 
Set the No. of repetitions. 
Repeated start (FOR condition) 
1 to 10 
Set the condition data No. (Data No. of 
"condition data" is set up for the 
condition judgment.)