6 - 2 
MELSEC-Q
 
6   PLC PROGRAM USED FOR POSITIONING CONTROL 
 
6.1 Precautions for creating program 
The common precautions to be taken when writing data from the PLC CPU to the 
QD75MH buffer memory are described below. 
When diverting any of the program examples introduced in this manual to the actual 
system, fully verify that there are no problems in the controllability of the target system. 
 
(1)   Reading/writing the data 
Setting the data explained in this chapter (various parameters, positioning data, 
block start data) should be set using GX Configurator-QP. 
When set with the PLC program, many PLC programs and devices must be 
used. This will not only complicate the program, but will also increase the scan 
time. 
When rewriting the positioning data during continuous path control or continuous 
positioning control, rewrite the data four positioning data items before the actual 
execution. If the positioning data is not rewritten before the positioning data four 
items earlier is executed, the process will be carried out as if the data was not 
rewritten. 
 
(2)   Restrictions to speed change execution interval 
Provide an interval of 100ms or more when changing the speed with the 
QD75MH. 
 
(3)   Process during overrun 
Overrun is prevented by the setting of the upper and lower stroke limits with the 
detail parameter 1. 
However, this applies only when the QD75MH is operating correctly. 
It is recommended to create an external circuit including a boundary limit switch 
to ensure the whole system safety as follows: the external circuit powers OFF 
the motor when the boundary limit switch operates.