9.2.17 Speed-position switching control (ABS mode) 
In case of "speed-position switching control (ABS mode)" ("
Da.2
 Control system = 
Forward run: speed/position, Reverse run: speed/position), the pulses of the speed set 
in "
Da.8
 Command speed" are kept output in the axial direction set to the positioning 
data. When the "speed-position switching signal" is input, position control to the 
address set in "
Da.6
 Positioning address/movement amount" is exercised. 
 
"Speed-position switching control (ABS mode)" is available in two different types: 
"forward run: speed/position" which starts the axis in the forward run direction and 
"reverse run: speed/position" which starts the axis in the reverse run direction. 
 
"Speed-position switching control (ABS mode)" is valid only when "
Pr.1
 Unit setting" 
is "2: degree". 
 
 Pr.1 
 Unit setting 
 
Speed-position  
function selection 
mm inch 
degree 
PLS 
INC mode 
 
 
 
 
ABS mode 
 
 
 
 
 
: Setting allowed,  
: Setting disallowed (If setting is made, an error (error code: 935) will occur when the PLC 
READY signal (Y0) turns ON.) 
 
Use the detailed parameter 1 "
 
Pr.81
 Speed-position function selection" to choose 
"speed-position switching control (ABS mode)". 
 
Buffer memory address 
Setting item 
Setting  
value 
Setting details 
Axis 1  Axis 2  Axis 3  Axis 4 
 Pr.81  
Speed-
position 
function 
selection 
Speed-position switching control 
(ABS mode) 
34 184 334 484 
 
 If the set value is other than 0 and 2, it is regarded as 0 and operation is performed in the INC 
mode. 
For details of the setting, refer to Sections 5.2 "List of parameters". 
 
 Switching over from speed control to position control 
 
(1)  The control is switched over from speed control to position control by the 
external signal "speed-position switching signal".  
(2)  Besides setting the positioning data, the "
Cd.24
 Speed-position switching 
enable flag" must also be turned ON to switch over from speed control to 
position control. (If the "
Cd.24
 Speed-position switching enable flag" turns 
ON after the speed-position switching signal turns ON, the control will continue 
as speed control without switching over to position control. Only position 
control will be carried out when the "
Cd.24
 Speed-position switching enable 
flag" and speed-position switching signal are ON at the operation start.)