11 - 10 
MELSEC-Q
 
11   MANUAL CONTROL 
 
11.2.4 Creating start programs for JOG operation 
A PLC program must be created to execute a JOG operation. Consider the "required 
control data setting", "start conditions" and "start time chart" when creating the 
program.  
The following shows an example when a JOG operation is started for axis 1. 
("
 Cd.17
JOG speed" is set to "100.00mm/min" in the example shown.) 
 
 Required control data setting 
 
The control data shown below must be set to execute a JOG operation. The 
setting is carried out with the PLC program.  
 
Buffer memory address 
Setting item 
Setting 
value 
Setting details 
Axis 
Axis 
Axis 
Axis 
 Cd.16 
 
Inching movement 
amount 
Set “0”. 
1517 1617 1717 1817 
 Cd.17
 JOG speed 
10000  Set a value equal to or below the "
 Pr.31
 
JOG speed limit value". 
1518 
1519 
1618 
1619 
1718 
1719 
1818 
1819 
 
                   Refer to Section 5.7 "List of control data" for details on the setting details. 
 
 Start conditions  
 
The following conditions must be fulfilled when starting. The required conditions 
must also be assembled in the PLC program, and the PLC program must be 
configured so the operation will not start if the conditions are not fulfilled.  
 
Device 
Signal name 
Signal state 
Axis 
Axis 
Axis 
Axis 
PLC READY signal 
ON  PLC CPU preparation completed 
Y0 
QD75 READY signal 
ON  QD75MH preparation completed 
X0 
All axis servo ON 
ON  All axis servo ON 
Y1 
Synchronization flag   ON 
QD75MH buffer memory 
The access is possible. 
X1 
Axis stop signal 
OFF  Axis stop signal is OFF 
Y4  Y5  Y6  Y7 
Start complete signal 
OFF  Start complete signal is OFF 
X10  X11  X12  X13 
BUSY signal 
OFF  QD75MH is not operating 
XC  XD  XE  XF 
Error detection signal 
OFF  There is no error 
X8  X9  XA  XB 
Interface 
signal 
M code ON signal 
OFF  M code ON signal is OFF 
X4  X5  X6  X7 
Forced stop input signal  ON  There is no forced stop input 
– 
Stop signal 
OFF  Stop signal is OFF 
– 
Upper limit (FLS)  
ON  Within limit range 
– 
External 
signal 
Lower limit (RLS)  
ON  Within limit range 
– 
 
 If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be 
inserted in the program for interlocking.  If it is set to the synchronous mode, it must not be 
inserted in the program for interlocking because it is turned ON when the PLC CPU executes 
calculation.