11   MANUAL CONTROL 
 
11.3.4 Creating a program to enable/disable the inching operation 
A PLC program must be created to execute an inching operation.  Consider the 
"required control data setting", "start conditions", and "start time chart" when creating 
the program. 
The following shows an example when an inching operation is started for axis 1. (The 
example shows the inching operation when a "10.0 µm" is set in "
 Cd.16 
Inching 
movement amount".) 
 
 Required control data setting 
 
The control data shown below must be set to execute an inching operation.  The 
setting is carried out with the PLC program. 
 
Buffer memory address 
Setting item 
Setting 
value 
Setting details 
Axis 
Axis 
Axis 
Axis 
 Cd.16 
 
Inching movement 
amount 
100 
Set the setting value so that the JOG speed 
limit value is not increased larger than the 
maximum output pulse 
1517 1617 1717 1817 
 
 Refer to Section 5.7 "List of control data" for information on setting details. 
 
 Start conditions 
 
The following conditions must be fulfilled when starting.  The required conditions 
must also be assembled in the PLC program, and the PLC program must be 
configured so the operation will not start if the conditions are not fulfilled. 
 
Device 
Signal name 
Signal state 
Axis 
Axis 
Axis 
Axis 
PLC READY signal 
ON  PLC CPU preparation completed 
Y0 
QD75 READY signal 
ON  QD75MH preparation completed 
X0 
All axis servo ON 
ON  All axis servo ON 
Y1 
Synchronization flag   ON 
Accessible to QD75MH buffer 
memory 
X1 
Axis stop signal 
OFF  Axis stop signal is OFF 
Y4  Y5  Y6  Y7 
Start complete signal 
OFF  Start complete signal is OFF 
X10  X11  X12  X13 
BUSY signal 
OFF  QD75MH is not operating 
XC  XD  XE  XF 
Positioning complete 
signal 
OFF 
Positioning complete signal is 
OFF 
X14 X15 X16 X17 
Error detection signal 
OFF  There is no error 
X8  X9  XA  XB 
Interface 
signal 
M code ON signal 
OFF  M code ON signal is OFF 
X4  X5  X6  X7 
Forced stop input signal  ON  There is no forced stop input 
– 
Stop signal 
OFF  Stop signal is OFF 
– 
Upper limit (FLS) 
ON  Within limit range 
– 
External 
signal 
Lower limit (RLS) 
ON  Within limit range 
– 
 
 If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be 
inserted in the program for interlocking.  If it is set to the synchronous mode, it must not be 
inserted in the program for interlocking because it is turned ON when the PLC CPU executes 
calculation.