11 - 31 
MELSEC-Q
 
11   MANUAL CONTROL 
 
11.4.2 Manual pulse generator operation execution procedure 
The manual pulse generator operation is carried out by the following procedure.  
 
   Write the PLC program created in STEP 1 and 
   STEP 2 to the PLC CPU using GX Developer. 
  
  Using GX Developer, set the control data and create a
  PLC program to enable/disable  the manual pulse 
  generator operation. (Set the control data in the QD75MH
  buffer memory using the TO command.) 
   One of the following two methods can be used. 
<Method 1>
Directly set (write) the parameters in the QD75MH using 
GX Configurator-QP. 
<Method 2> 
Set (write) the parameters from the PLC CPU to the 
QD75MH using the PLC program (TO command).
STEP 1
 
 
 
Manual pulse
generator operation
start
 
 
 
 
End of control
 
 
 
STEP 2
 
 
 
STEP 3
 
 
 
STEP 4
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
STEP 5
 
 
 
 
 
 
 
 
 
Issue a command to enable the manual pulse generator
operation, and input the signals from the manual pulse
generator. 
 
End the input from the manual pulse generator, 
and issue a command to disable the manual pulse 
 
Manual pulse
generator operation
stop
 
 
STEP 6
Monitor the manual pulse generator operation.
 
Preparation
Refer to Chapter 5
and Section 11.4.3.
Refer to Section
11.4.4.
Set the positioning parameters 
Write the PLC program to the PLC CPU.
   One of the following two methods can be used. 
<Method 1>
Monitor using GX Configurator-QP.
<Method 2>
Monitor using GX Developer. 
Monitoring of the
manual pulse
generator operation
Set " Cd. 20  Manual pulse generator 1 pulse input
magnification". (control data setting)
to
)
Pr.1
)
Pr.24
Create a PLC program in which the enable/disable is
 
 
(" Cd. 21  Manual pulse generator enable flag" setting.)
set for the manual pulse generator operation. 
  Stop operating the manual pulse generator, and write "0"
  in " Cd. 21 Manual pulse generator enable flag".
 
 
 
    Write "1" in " Cd.21  Manual pulse generator enable 
    flag", and operate the manual pulse generator. 
 
 
 
 
 
REMARK 
 Mechanical elements such as limit switches are considered as already installed.  
 Positioning parameter settings work in common for all control using the QD75MH.