12 - 39 
MELSEC-Q
 
12   CONTROL SUB FUNCTIONS 
 
12.4.5 Forced stop function 
 
!
 DANGER 
 When the forced stop is required to be wired, ensure to wire it in the negative logic using b-contact. 
 Provided safety circuit outside the QD75MH so that the entire system will operate safety even when the 
"
 
Pr.82
 Forced stop valid/invalid" is set "1: Invalid". Be sure to use the forced stop signal (EMI) of the 
servo amplifier. 
 
By the QD75MH external equipment connector is connected forced stop, this function 
is available for all axes of servo amplifier. (The initial value is "0: Valid".) 
The forced stop input valid/invalid is selected by "
 
Pr.82
 Forced stop valid/invalid". 
 
The details shown below explain about the "forced stop function".  
  [1] Control details 
  [2] Wiring the forced stop 
  [3] Setting the forced stop 
  [4] How to check the forced stop 
  [5] Precautions during control 
 
[1]   Control details 
A warning "controller forced stop warning (warning code: 2147)" will occur if 
turned on the forced stop input signal when the "
 
Pr.82
 Forced stop valid/invalid" 
is set "0: Valid". And then it is available for all axes of servo amplifier. 
 
The outline of the forced stop process is shown below. 
 
Stop process 
OPR control 
Manual control 
Stop cause 
Stop 
axis 
M code 
ON 
signal 
after stop 
Axis 
operation 
status 
(
Md.26
after 
stopping 
Machine 
OPR 
control 
Fast OPR 
control 
Major 
positioning 
control 
High-level 
positioning 
control 
JOG/ 
Inching 
operation 
Manual 
pulse 
generator 
operation 
Forced stop 
"Forced stop input 
signal" OFF 
All axes 
No 
change 
Servo OFF 
Servo OFF or free run (The operation stops with dynamic 
brake)