12 - 50 
MELSEC-Q
 
12   CONTROL SUB FUNCTIONS 
 
[2]   Precaution during control 
(1)  When changing the speed during continuous path control, the speed change 
will be ignored if there is not enough distance remaining to carry out the 
change.  
(2)  A warning "Deceleration/stop speed change (warning code: 500)" occurs 
and the speed cannot be changed in the following cases. 
(The value set in "
Cd.13
Positioning operation speed override" is validated 
after a deceleration stop.) 
 During deceleration by a stop command 
 During automatic deceleration during positioning control 
(3)  When the speed is changed during interpolation control, the required speed 
is set in the reference axis. 
(4)  When deceleration is started by the override function, the deceleration start 
flag does not turn ON. 
(5)  When carrying out continuously override, be sure there is an interval 
between the override execution of 100ms or more. 
(If the interval between override is short, the QD75MH will not be able to 
track, and it may become impossible to carry out commands correctly.) 
 
[3]   Setting the override function 
The following shows the data settings and PLC program example for setting the 
override value of axis 1 to "200%". 
(1)  Set the following data. (Use the start time chart shown in section (2) below 
as a reference, and set using the PLC program shown in section (3).)  
 
Buffer memory address 
Setting item 
Setting 
value 
Setting details 
Axis 
Axis 
Axis 
Axis 
Cd.13
 
Positioning 
operation speed 
override 
200 
Set the new speed as a percentage (%). 
1513  1613  1713  1813 
 
                   Refer to Section 5.7 "List of control data" for details on the setting details.