15 - 52 
MELSEC-Q
 
15   TROUBLESHOOTING 
 
 
 
Classification 
of warnings 
Warning 
code 
Warning name 
Warning 
Operation status at warning 
occurrence 
 
Manual pulse 
generator 
operation 
warnings 
401 
Outside manual 
pulse generator 
input magnification 
range 
The manual pulse generator 1 pulse 
input magnification is set at 0 or 
1001 or higher. 
• When input magnification is set at 
1001 or higher:  Re-set to 1000. 
• When input magnification is set at 0: 
Re-set to 1. 
 
 
 
 
500 
Deceleration/stop 
speed change 
The speed change request is issued 
during deceleration stop. 
The speed change is not carried out. 
 
 
 
 
 
 
 
501 
Speed limit value 
over 
The new value exceeds the speed 
limit value when the speed is 
changed during operation. 
• The speed is controlled with the 
speed limit value. 
• The "speed limiting flag" is turned 
ON. 
 
 
 
 
 
 
503 
M code ON signal 
ON start 
The M code ON signal is turned ON 
when the positioning data is 
executed. 
Continue executing the positioning 
data. 
 
 
 
505 
No operation 
termination setting 
In the positioning by block starting, 
the 50th point of the positioning start 
data is set to CONTINUE. 
The operation is terminated. 
 
 
 
 
506 
FOR to NEXT nest 
construction 
FOR to NEXT is nested. 
 
 
508 
Speed-position 
switching (during 
acceleration) signal 
ON 
The switching signal for speed-
position switching control (INC 
mode) is turned ON during 
acceleration. 
The operation is continued. 
 
 
 
 
509 
Insufficient 
remaining distance 
• At a continuous operation interrupt 
request, the distance required 
deceleration stop is not long 
enough. 
• At a speed change request, the 
remaining distance is shorter than 
the distance required for speed 
change. 
• When a command speed is 
changed:  
    Change to a value as near a new  
    speed value as possible. 
• When a target position is changed:  
    Adjust the speed to a value as  
    near the command speed as  
    possible, and then change to a  
    target position. 
(When the operation pattern is a 
continuous path control, ignore the 
operations stated above.) 
 
 
 
 
 
 
 
 
 
 
 
 
511  Step not possible 
Code 1 is set for the step start 
information when the step is outside 
standby. 
The step will not start. 
 
 
 
512 
Illegal external 
command function 
The detailed parameter 2 "External 
command function selection" setting 
range is exceeded. 
Even if the external command signal 
is turned ON, the system will not 
perform anything. 
 
 
 
Positioning 
operation 
warnings 
513 
Insufficient 
movement amount 
The movement amount is not large 
enough for automatic deceleration. 
The system stops immediately after it 
reaches the positioning address.