15   TROUBLESHOOTING 
 
15.4 LED display functions 
The states of QD75MH and each axis control can be confirmed by the LEDs located 
on the front panel of the QD75MH main unit. 
 
QD75MH4
RUN
ERR
AX1
AX2
AX3
AX4
 
 
Each axis can be monitored by the states of the LEDs. 
The operation and indications of the LEDs are as shown below. 
 
Details of indication 
Goes OFF   
Goes ON   
Flashes   
Points to be 
confirmed 
Error Remedy 
RUN
ERR
AX1
AX2
AX3
AX4
 
Extinguishment of 
RUN LED 
The hardware is 
faulty or watch dog 
timer error occurs. 
If the RUN LED does not light up even when the 
power is turned ON, the module may be out of order.  
Replace the module with a new one. 
RUN
ERR
AX1
AX2
AX3
AX4
 
Lighting of RUN LED, 
Extinguishment of 
ERR LED 
The module is 
normal. 
— 
RUN
ERR
AX1
AX2
AX3
AX4
 
Lighting of ERR LED  System error 
An operation condition setting error or installation PLC 
CPU type error occurs. 
(The setting and PLC CPU type are outside the 
specification range.) Set the PLC CPU type to a one 
contained in the specification. 
RUN
ERR
AX1
AX2
AX3
AX4
 
Extinguishment of 
AX1 to AX4 LEDs 
During axis stop, 
during axis standby 
— 
RUN
ERR
AX1
AX2
AX3
AX4
 
Lighting of AX1 
(Same even if the 
other axis is lit) 
During axis 
operation 
This lights up from the positioning start until the 
positioning is completed, stopped temporarily, or 
stopped by error (corresponding at a ratio of 1 : 1 to 
BUSY signals). 
RUN
ERR
AX1
AX2
AX3
AX4
 
Flashing of ERR LED 
Flashing of AX1 LED 
(Same even if the 
other axis flashes) 
Axis error 
Check the error observed on the buffer memory batch 
processing monitor of a peripheral device and correct 
the applicable parameters and positioning data. 
RUN
ERR
AX1
AX2
AX3
AX4
 
Lighting of all LEDs 
The hardware is 
faulty 
The module comes out of order.  Replace the module 
with a new one.