Appendix - 36 
MELSEC-Q
 
APPENDICES 
 
Appendix4.2 Wiring of manual pulse generator cable 
There are no our option in the manual pulse generator. The manual pulse generator 
cable fabricate on the customer side. 
 
(1)   Manual pulse generator cable  
The following table indicates the manual pulse generator cables used with motion 
controller and the manual pulse generator. Make selection according to your 
operating conditions. 
Table 1 Table of wire specifications 
Characteristics of one core 
Wire model 
Core 
size 
[mm
2
Number of 
cores 
Structure 
[Number of 
wires/mm] 
Conductor 
resistance 
[ /km] 
Insulating 
sheath OD 
d[mm] 
(Note-1)
 
Finish OD 
[mm] 
(Note-2)
 
17/0.16-6P-SRV-SV(2464)K 
0.3 
12(6 pairs) 
17/0.16 
Max. 57.5 
1.26 
8.4 
NFKEV-SB  0.3 mm
2
4P 0.3 
8(4 
pairs) 
7/0.127 Max. 
66.3  1.30 7.6 
 
(Note-1): d is as shown below. 
Insulation sheath
Conductor
d
 
(Note-2): Standard OD. Max. OD is about 10% larger. 
 
(a)   Connection diagram 
When fabricating a cable, use the recommended wire given on (1), and 
make the cable as show in the following connection diagram. The overall 
distance of the manual pulse generator cable on the same bus is 
30m(98.4ft.) . 
(Note): Connect the shield to ground only on the manual pulse generator 
side. (Only one side is connected.) 
 
 
QD75MH
Manual pulse
generator
Shield
A phase
Pin No.
1B19
1B20
1B15
A
B
5V
0V
1A15
:Twisted pair cable
5V
1B14
1A14
0V
B phase
 
 
 
!
 CAUTION 
 When fabricating the cable, do not make incorrect connection. Wrong connection will cause runaway or 
explosion.