3 - 20 
MELSEC-Q
 
3   SPECIFICATIONS AND FUNCTIONS 
 
3.4.3 List of input signal details 
The details of each QD75MH external device connection connector are shown below: 
 
Pin No. 
Signal name 
AX1 AX2 AX3 AX4 
Signal details 
(Negative logic is selected by external input signal logic selection) 
Manual pulse generator A 
phase 
Manual pulse generator B 
phase 
1A19 
1A20 
— 
• Input the pulse signal from the manual pulse generator A phase and B 
phase. 
• If the A phase leads the B phase, the positioning address will increase at the 
rising and falling edges of each phase. 
• If the B phase leads the A phase, the positioning address will decrease at the 
rising and falling edges of each phase. 
[When increased] 
[When decreased] 
Manual pulse generator A 
common 
Manual pulse generator B 
common 
1B19 
1B20 
— 
+1+1+1+1+1+1+1+1
-1 -1 -1 -1 -1 -1 -1 -1
A phase
B phase
Positioning
address
A phase
B phase
Positioning
address
 
Upper limit signal 
1A1  1B1  2A1  2B1 
• This signal is input from the limit switch installed at the upper limit position of 
the stroke. 
• Positioning will stop when this signal turns OFF. 
• When OPR retry function is valid, this will be the upper limit for finding the 
near-point dog signal. 
Lower limit signal 
1A2  1B2  2A2  2B2 
• This signal is input from the limit switch installed at the lower limit position of 
the stroke. 
• Positioning will stop when this signal turns OFF. 
• When OPR retry function is valid, this will be the lower limit for finding the 
near-point dog signal. 
Near-point dog signal 
1A3  1B3  2A3  2B3 
• This signal is used for detecting the near-point dog during OPR. 
• The near-point dog OFF   ON is detected at the rising edge. 
• The near-point dog ON   OFF is detected at the falling edge. 
Stop 
signal 
1A4 1B4 2A4 2B4 
• Input this signal to stop positioning. 
• When this signal turns ON, the QD75MH will stop the positioning being 
executed. 
After that, even if this signal is turned from ON to OFF, the system will not 
start. 
External command signal/ 
switching signal 
1A5 1B5 2A5 2B5 
• Input a control switching signal during speed-position or position-speed 
switching control. 
• Use this signal as the input signal of positioning start, speed change request, 
and skip request from an external device. 
Set the function to use this signal in "
Pr.42
External command function 
selection". 
Common 
1A6 
1A7 
1B6 
1B7 
2A6 
2A7 
2B6 
2B7 
• Common for upper/lower limit, near-point dog, stop, and external command 
signal/switching signals. 
Forced stop input signal 
1A8 
— 
Forced stop input signal 
common 
1B8 — 
• This signal is input when batch forced stop is available for all axes of servo 
amplifier. 
• When this signal turns OFF, the QD75MH will be the forced stop. 
Manual pulse generator power 
supply (+ 5VDC) 
1A15 
1B15 
— 
• Power supply for manual pulse generator. (+ 5VDC) 
Manual pulse generator power 
supply (GND) 
1A14 
1B14 
— 
• Power supply for manual pulse generator. (GND)