Appendix 6 Positioning control troubleshooting 
Trouble type 
Questions/Trouble 
Remedy 
No. 
Display reads "FFFF
H
" when a 
parameter is read with GX 
Configurator-QP. 
The PLC CPU power was turned OFF or the PLC CPU 
was reset, etc., during flash ROM writing, which deleted 
the data in the flash ROM.  
Initialize the parameters, and reset the required 
parameters.  
(Refer to Section 13.2 "Parameter initialization function" 
for details.) 
How can the parameters be 
returned to their initial values ? 
Set the "
Cd.2
Parameter initialization request" to "1". 
(Refer to Section 13.2 "Parameter initialization function" 
for details.) 
Parameter 
A parameter error occurred 
although the parameter was set 
correctly by GX Configurator-QP. 
The parameter may have been overwritten in the PLC 
program. 
Review the PLC program. 
The machine overruns if operating 
at high speeds when the hardware 
stroke limit range is exceeded. 
In the QD75MH, deceleration stops are executed after the 
machine exceeds hardware stroke limit range. Because of 
this, more time is required for the deceleration stop as the 
speed increases, and the overrun becomes larger. 
(The deceleration time becomes shorter at lower speeds, 
so the overrun becomes smaller.) 
Hardware stroke limit 
When the machine exceeded the 
hardware stroke limit range, 
positioning toward inside the range 
was started, but the machine did 
not start. 
Use a "JOG operation", " Inching operation" or "Manual 
pulse generator operation" to return the machine to inside 
the hardware stroke limit range. 
(When the hardware stroke limit range is exceeded, 
positioning will not start toward inside the range even 
when so commanded.  Once the range is exceeded, a 
return to inside the range can only be executed using a 
"JOG operation", "Inching operation" or "Manual pulse 
generator operation".) 
Degree 
Exactly one rotation is required, 
but the setting range for a "degree" 
unit setting is "0 to 359.999...". 
Won't the rotation deviate by 
"0.00...1"? 
Designate "360.000" in the INC control. 
The motor will make exactly one rotation. 
Movement amount 
per pulse 
If the "movement amount per 
pulse" is calculated as written in 
the manual, settings smaller than 
the basic parameter setting range 
cannot be carried out.  
Set "movement amount per pulse" in the QD75MH using 
the three parameter values of 
Pr.2
 to 
Pr.4
Try setting the values following the explanations for each 
parameter. 
Will an override setting value 
written before starting be valid? 
It will be valid. 
During path control, will the 
override still be valid after the point 
is passed? 
It will still be valid. 
Override 
How can the override be 
canceled? 
Set the "
Cd.13
Positioning operation speed override" to 
"100". 