4   INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT 
 
4.3 Wiring 
The precautions for wiring the QD75MH are given below. Refer to this section as well 
as "4.1.3 Handling precautions" when carrying out the work. 
 
4.3.1 Precautions for wiring 
DANGER
 
 Completely turn off the externally supplied power used in the system before installation or 
wiring. Not doing so could result in electric shock or damage to the product. 
 
CAUTION
 
 Check the layout of the terminals and then properly route the wires to the module. 
 Connectors for external input signal must be crimped with the tool specified by the 
manufacturer, or must be correctly soldered. Insufficient connections may cause short circuit, 
fire, or malfunction. 
 Be careful not to let foreign matter such as sawdust or wire chips get inside the module. These 
may cause fires, failure or malfunction. 
 The top surface of the module is covered with protective films to prevent foreign objects such as 
cable off cuts from entering the module when wiring. Do not remove this film until the wiring is 
complete. Before operating the system, be sure to remove the film to provide adequate 
ventilation. 
 Securely connect the connector for SSCNET  cable to the front connector on the module. 
 When removing the cable from the module, do not pull the cable. Hold the connector that is 
connected to the module. Pulling the cable that is still connected to the module may cause 
malfunction or damage to the module or cable. 
 The external input/output signal cable and the communication cable should not be routed near 
or bundled with the main circuit cable, power cable and/or other such load - carrying cables 
other than those for the PLC. These cables should be separated by at least 100mm (3.94inch) 
or more. They can cause electrical interference, surges and inductance that can lead to mis-
operation. 
 The shielded cable for connecting QD75MH can be secured in place. If the shielded cable is not 
secured, unevenness or movement of the shielded cable or careless pulling on it could result in 
damage to the QD75MH, servo amplifier or shielded cable or defective cable connections could 
cause mis-operation of the unit. 
 If the cable connected to the QD75MH and the power line must be adjacently laid (less than 
100mm (3.94inch)), use a shielded cable. Ground the shield of the cable securely to the control 
panel on the QD75MH side. (A wiring example is given on this section "[1] Precautions for 
wiring"). 