  Safety   
6Safety
Fig.6-5 : Example of safety measures (CR750 wiring example 5)
OP
E-stop
1
2
3
4
5
6
CNUSR11
内部リレー
TB
E-stop
24G
1
2
3
4
5
6
24G
内部リレー
X0
COM0
X1
COM1
No connection
No connection
安全入力1
安全入力2
24V DC
24G
例)QS90SR2SP
  ( 三菱電機株式会社)
安全リレー
お客様電源(DC 24V)
+24V
24G
お客様装置
24V DC
外部非常停止スイッチ
13
14
24V DC
24V DC
外部非常停止スイッチ
13
14
24V DC
安全リレー
非常停止出力
非常停止出力
CNUSR12
No connection
No connection
Controller
Safety relay
*2)
<Wiring example 5>: Connect the controller to the safety relay 
Use the controller’s emergency stop button command as an input to the safety relay.
Internal relay
Emergency stop 
output
Internal relay
External emergency stop switch
External emergency stop 
switch
Emergency stop 
output
Customer equipment
Safety relay
ex) QS90SR2SP (Mitsubishi 
Electric Corporation)
Safety 
input 1
Customer Power Supply (DC 24V)
[Caution]
1) This product has category 3 functionality and therefore the robot’s whole unit cannot be set to category 4.
2) The controller’s internal circuit has polarity. Please adhere to the polarity as detailed in the wiring examples, 
particularly for emergency stop button output when using user equipment. Connect the positive side of the 
user equipment (24V DC) to the terminal 2 of CNUSR11/12, then connect the emergency stop button (or 
contact points) in the user equipment to across the terminals 3 and 4 of CNUSR11/12, and ultimately con
-
nect the negative side (24G).
3) When installing a safety relay to use it as an input point of the controller's emergency stop button command, 
use a safety relay that is activated by an input from one of the two systems (i.e. QS90SR2SP (Manufacture: 
Mitsubishi Electric Corporation)).
4) The emergency stop input detection relay (internal relay) uses the controller’s internal safety relay control. 
If the emergency stop input detection relay is switched OFF, emergency stop is detected and the safety 
relay is also switched OFF.
5) When connecting emergency stop button output to an external safety relay, please take note of the polarity 
and make sure that the electrical current flows in the same direction as indicated by the dotted arrows in the 
two places in the diagram. If the polarity is setup incorrectly, this function will not operate correctly. Please 
connect the terminal 13 of CNUSR11/12 to 24V.
Safety 
input 2