AVR Trim 
 
This LED illuminates to indicate the UPS is compensating for a 
high utility voltage. 
AVR Boost 
 
This LED illuminates to indicate the UPS is compensating for a low 
utility voltage. 
B
ATTERY 
P
OWER
 
If the utility power fails, the UPS can provide power to the connected equipment from its internal 
battery for a finite period. The UPS sounds an alarm—four beeps every 30 seconds—while operating 
on battery power. The alarm stops when the UPS returns to online operation. 
On Battery  
 
When the on battery power LED is lit the UPS is supplying battery 
power to the connected equipment. 
Battery Charge 
 
The five-LED display on the right of the front panel shows the present 
charge of the UPS battery as a percentage of the battery capacity. 
When all five LEDs are lit, the battery is fully charged. The LEDs ex-
tinguish, from top to bottom, as the battery capacity diminishes. Refer 
to the figure at left for the battery capacity threshold (values are not 
listed on the UPS). 
As a low battery warning, any LEDs illuminated (for the given capac-
ity) flash and the UPS beeps. The low battery warning default setting 
can be changed from the rear panel or through the optional Power-
Chute software. Refer to Default Settings below for details. 
Overload 
 
The UPS emits a sustained alarm tone and the LED illuminates when 
an overload condition occurs. Refer to Troubleshooting in this manual. 
Replace Battery 
 
Failure of a battery self-test causes the UPS to emit short beeps for one 
minute and the replace battery LED illuminates. Refer to Trouble-
shooting
 in this manual. 
S
HUTDOWN 
M
ODE 
(
VIA SOFTWARE OR AN ACCESSORY
In shutdown mode, the UPS stops supplying power to the connected equipment, waiting for the re-
turn of utility power. If there is no utility power present, external devices (such as servers) connected 
to the computer interface or the accessory slot can command the UPS to shut down. This normally is 
done to preserve battery capacity after the shutdown of protected servers. The UPS scrolls the front 
panel LEDs sequentially in shutdown mode.