Справочник Пользователя для American Power Conversion SL-300TFX
15
N
OTE
: S
ETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
High Transfer
Point
Point
230V models:
253VAC
253VAC
120V models:
132VAC
100V models:
110VAC
230V models:
264, 271,
280VAC
264, 271,
280VAC
120V models:
129, 135,
138VAC
129, 135,
138VAC
100V models:
108, 112,
114VAC
108, 112,
114VAC
To avoid unnecessary battery usage, set
the high transfer point higher if the util-
ity voltage is chronically high and the
connected equipment is known to work
under this condition.
the high transfer point higher if the util-
ity voltage is chronically high and the
connected equipment is known to work
under this condition.
Low Transfer
Point
Point
230V models:
196VAC
196VAC
120V models:
103VAC
100V models:
90VAC
90VAC
230V models:
188, 204,
208VAC
188, 204,
208VAC
120V models:
97, 100, 106VAC
97, 100, 106VAC
100V models:
81, 85, 92VAC
81, 85, 92VAC
Set the low transfer point lower if the
utility voltage is chronically low and the
connected equipment can tolerate this
condition.
utility voltage is chronically low and the
connected equipment can tolerate this
condition.
Output Voltage
230V models:
230VAC
230VAC
230V models:
220, 225,
240VAC
220, 225,
240VAC
230V models only; allow the user to se-
lect the output voltage.
lect the output voltage.