15
N
OTE
: S
ETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE
.  
F
UNCTION
 
F
ACTORY
 
D
EFAULT
 
U
SER 
S
ELECTABLE 
C
HOICES
 
D
ESCRIPTION
 
High Transfer 
Point 
230V models: 
253VAC  
 
120V models: 
132VAC 
 
100V models: 
110VAC 
230V models: 
264, 271, 
280VAC 
120V models: 
129, 135, 
138VAC 
100V models: 
108, 112, 
114VAC 
To avoid unnecessary battery usage, set 
the high transfer point higher if the util-
ity voltage is chronically high and the 
connected equipment is known to work 
under this condition. 
Low Transfer 
Point 
230V models: 
196VAC 
 
120V models:
 
103VAC 
100V models: 
90VAC 
230V models: 
188, 204, 
208VAC 
120V models: 
97, 100, 106VAC 
100V models: 
81, 85, 92VAC 
Set the low transfer point lower if the 
utility voltage is chronically low and the 
connected equipment can tolerate this 
condition. 
Output Voltage 
230V models: 
230VAC 
230V models: 
220, 225, 
240VAC 
230V models only; allow the user to se-
lect the output voltage.