Chapter 1  System Description      5 
ACTURA Flex 48330
 
Power System  User Manual 
The Dimension of Rectifier Shelf are given in Table 1-2 
Table 1-2  Dimensions of rectifier shelf 
Manufacture type 
W(mm) ×D(mm) ×H(mm) 
Note 
PSS485023/C 584.2×327×132.5 
23’’ 
with 
controller 
 
Backboard 
The backboard has the functions below: 
  DC power source feed for controller and the connector board. 
  DC input filter and input fuse. 
  All the ingoing and outgoing signals of the controller 
The backboard also contains system internal connectors below: 
  10 Distribution unit fuses alarm signal measurement input 
  4 battery fuse alarm signal measurement input   
  2 battery current shunt measurement inputs 
  1 load Current shunt measurement input 
  System bus-bar DC Voltage measurement input 
  Three-phase from two mains AC Voltage measurement inputs 
  CAN communication between rectifiers and controller 
  AC alarm module signals 
  System fault indicator drivers 
  LLVD & BLVD mono contactor driver outputs 
  The entire signal outgoing to the connector board 
Connector board   
Connector board is a user interface board and has the functions below: 
  8-channel relay outputs 
  8-channel digital inputs 
  One power source feed terminal (for digital inputs) 
  2-channel temperature sensor inputs 
  2-channel RS232 parallel connection outputs 