8            Chapter 1    System Description 
ACTURA Flex 48330
 
Power System  User Manual 
When SCU communicates with MC through MODEM or ES-MOD, it uses PSTN to 
realize long-distance monitoring. Power supply cables and communication cables 
shall be prepared for the communication through MODEM. 
3. Dry Contacts Output 
SCU has 8 dry-contact outputs. Every dry-contact output has NC (normally closed) 
and NO (normally-open) contacts. Every dry-contact output shall be configured 
before the alarm event occurs. Different dry-contact output can trigger different 
alarms. Once the alarm event occurs, the dry-contact will close or open to generate 
the alarm. 
If the user has other intelligent equipment to be monitored by SCU, the user can 
connect the dry contacts to the interface of the intelligent equipment, and control 
the intelligent equipment through these dry contacts. 
Capacity of dry contacts: 2A@30Vdc; 05A@125Vac;   
Maximum power dissipation: 60W 
Functions fulfilled by SCU and MC 
In RS232 and MODEM communication modes, the MC can fulfill the following 
functions through SCU: 
1. Remote acquisition of analog and digital values: MC can acquire the real-time 
analog and digital values of DC Power System through SCU; 
2. Remote control functions: MC can shut down the rectifiers, change the boost 
charge status to float charge status (or in reverse), silence the alarm and stop/start 
the battery test through SCU. 
Alarm category settings for dry contact output 
1. Through setting the parameter of “Relate Relay”, the user can configure the 
alarm category for every dry-contact output. Every dry-contact output has been 
configured to correspond to an alarm category before SCU is delivered to 
customer. 
2. SCU has PLC functions in the alarm management. The PLC is to realize simple 
logic operation, i.e. the "And", "Or" and "Not" operations. The PLC inputs are all the 
possible alarm signals, and the PLC outputs can be used to select one of the 8 dry 
contacts. The alarm categories can be configured flexibly for every dry-contact 
output through MC. The PLC settings for every dry-contact have three alarm inputs, 
and two relation flag. The SN of three alarm categories and the mutual logic 
relationships need to be configured. 
PLC can be set to “Disabled”. If PLC functions and alarm co-relation are enabled at 
the same time, the dry contact will act to activate an alarm when any alarm event 
occurs.