12      Chapter 2  Installation 
ACTURA Flex 48330
 
Power System  User Manual 
Chapter 2  Installation 
2.1  Installation Preparation 
2.1.1  Environmental Conditions 
Make sure the following environmental conditions are satisfied when selecting the 
installation site: 
Table 2-1    Environmental conditions in power room 
Environmental conditions 
Recommended range 
Ambient temperature 
-5~50°C (If ambient temperature > 45°C, for the cabinet with 
400mm depth, it should demount the front door of cabinet to 
ensure the normal operation of the system.)   
Humidity 
≤90%RH, non-condensing 
Dust 
≤1mg/m
3
 
Sunlight 
No direct sunlight 
Corrosives 
No pollutants, such as salt, acid, and smoke, etc. 
Shake 
≤1.5m/s
2
 
Insects, pests, and termites 
None 
Mildew None 
Moisture Water 
proof 
Fire protection 
No flammable on the top/bottom of the cabient. 
 
The DC Power system will be damaged if dust or sand accumulates in it. The 
following measures are recommended for dusty environment: 
1.The system should be installed in an airtight and air-conditioned power room. The 
air-conditioner filter should be well serviced without being obstructed. To reduce the 
dust in the power room, un-attendance in the power room is recommended. 
2.The air filter should be cleaned periodically. 
3.The product should be installed on a cement ground. 
2.1.2  Power Supply 
AC power supply for communication uses AC mains as its main power source. 
Backup batteries and generator should be configured according to the actual power 
supply situation. The AC power supply system composed of AC mains and 
generator should adopt centralized power supply mode to supply power, while low