Chapter 5  Operating SCU      53 
ACTURA Flex 48330
 
Power System  User Manual 
The maintenance operations over a single rectifier include: “DC ON/OFF”, “AC 
ON/OFF” and “Reset”. The operation method is:   
① Use “
” or ”
” to select the rectifier parameter, and “
” or “
” to change the 
rectifier serial No. Then press “ENT” to confirm. The bottom line of the page 
displays the rectifier ID.   
② Use “
” or “
” to move the cursor to the maintenance operation area, and 
” or “
” to select the value.   
If the rectifier voltage is too high, you can select “Reset” to restore the output 
voltage of that rectifier to normal.   
6. There will be prompts as the confirmation of control commands. If the 
maintenance operation is valid, system will prompt you press “ENT” to confirm and 
execute the operation, or “ESC” to abort the operation. Otherwise, system will 
prompt you the operation is invalid, and press “ESC” to quit.   
   
Press ENT to Run 
       
Other Key Quit 
 
 
 
No Maintain! 
 
ESC Quit 
 
 
Press “ESC” to return to the menu of higher level.   
5.7    Setting System Parameters 
Battery parameters are very important, for they are related to the life of battery. 
Before delivery, the battery parameters have been initialized. Without any special 
needs, you only need to reset the battery group number and battery capacity, and 
accept the defaults for other parameters.     
5.7.1  Parameter Setting Method 
1. At any system information page, press “ENT” to enter the main menu.   
MAIN MENU               
status    
Maintenance 
Settings