Справочник Пользователя для GE GEK-106465A

Скачать
Страница из 43
I/O MODULES DESCRIPTION  
 
32 
CIO Remote CAN Digital I/O Module 
  GEK-106465A 
5.2. CONTROL 
SETTINGS FOR INPUTS/OUTPUTS 
This section explains the settings related to CIO inputs/outputs. Modification of these values is performed using the 
master unit communication software, EnerVista F650Setup for F650, or GE-CONF for F600. 
 
5.2.1. 
INPUT/OUTPUT BOARDS SETTINGS 
Settings relative to I/O boards are described in table 5-1: 
TABLE  5-1 I/O BOARD SETTINGS 
SETTING 
HMI 
DEFAULT 
RANGE 
STEP 
16 INP + 8OUT 
8 INP + 8OUT + 
SUPV 
I/O board type (available only for 
CIO modules) 
I/O Board_X Type 
NONE 
NONE 
N/A 
Input activation voltage threshold 
Group A 
Voltage Threshold A_X 
80 
0 – 255 V 
1 V 
Input activation voltage threshold 
Group B 
Voltage Threshold B_X 
80 
0 – 255 V 
1 V 
Debounce time Group A 
Debounce Time A_X 
15 
1 – 50 ms 
1 ms 
Debounce time Group B 
Debounce Time B_X 
15 
1 – 50 ms 
1 ms 
POSITIVE-EDGE 
NEGATIVE-EDGE 
POSITIVE 
Input type 
Input Type_X_CCY POSITIVE 
NEGATIVE 
N/A 
Input signal time delay 
Delay Input 
Time_X_CCY 
0 – 60000 ms 
1 ms 
Output logic type 
Output Logic_X_0Z POSITIVE 
POSITIVE- 
NEGATIVE 
N/A 
NORMAL 
PULSE 
Output type 
Output Type_X_0Z NORMAL 
LATCH 
N/A 
Output pulse length 
Pulse Output 
Time_X_0Z 
0 – 60000 ms 
1 ms 
 
Being: 
X  
I/O board name, depending on the CIO model. 
For the I/O board selection in the relay model, associated digits to each board type are as follows: 
 
ASSOCIATED DIGIT 
F650PC BOARD 
SETTINGS 
BOARD TYPE 
0 NONE 
None 
16 INP+ 8OUT 
Mixed 
8 INP +8 OUT +SUPV 
Supervision