Справочник Пользователя для DELL H967N

Скачать
Страница из 71
43
 
Operation
|
Description
Default Setting
Available Settings
Battery Saving Mode
[Disabled] [10%] [20%] [30%]...[100%]
The UPS output is turned off in five minutes if the
UPS is on battery and output power is below the
selected level.
Disabled
On Battery Notice Delay
[0] [1s] [2s]...[99s]
The UPS issues a “UPS on battery” notice in the
specified number of seconds after the UPS starts to
discharge the batteries.
0s
Site Wiring Fault Alarm
[Enabled] [Disabled]
Enabled for low
voltage models;
Disabled for all other
models
Bypass Voltage Low Limit
[-6%] [-7%]...[-20%] of nominal
The Bypass operation is disabled if the measured
bypass voltage level is below the nominal output
voltage (-15%).
NOTE:
 The Qualify Bypass setting may overrule the
Bypass Voltage Low Limit setting.
-15% of nominal
Bypass Voltage High Limit
[+6%] [+7%]...[+20%] of nominal
The Bypass operation is disabled if the measured
bypass voltage level is above the nominal output
voltage (+10%).
NOTE:
 The Qualify Bypass setting may overrule the
Bypass Voltage High Limit setting.
+10% of nominal