Справочник Пользователя для DELL H967N
43
Operation
|
Description
Default Setting
Available Settings
Battery Saving Mode
[Disabled] [10%] [20%] [30%]...[100%]
The UPS output is turned off in five minutes if the
UPS is on battery and output power is below the
selected level.
UPS is on battery and output power is below the
selected level.
Disabled
On Battery Notice Delay
[0] [1s] [2s]...[99s]
The UPS issues a “UPS on battery” notice in the
specified number of seconds after the UPS starts to
discharge the batteries.
specified number of seconds after the UPS starts to
discharge the batteries.
0s
Site Wiring Fault Alarm
[Enabled] [Disabled]
Enabled for low
voltage models;
Disabled for all other
models
voltage models;
Disabled for all other
models
Bypass Voltage Low Limit
[-6%] [-7%]...[-20%] of nominal
The Bypass operation is disabled if the measured
bypass voltage level is below the nominal output
voltage (-15%).
bypass voltage level is below the nominal output
voltage (-15%).
NOTE:
The Qualify Bypass setting may overrule the
Bypass Voltage Low Limit setting.
-15% of nominal
Bypass Voltage High Limit
[+6%] [+7%]...[+20%] of nominal
The Bypass operation is disabled if the measured
bypass voltage level is above the nominal output
voltage (+10%).
bypass voltage level is above the nominal output
voltage (+10%).
NOTE:
The Qualify Bypass setting may overrule the
Bypass Voltage High Limit setting.
+10% of nominal