Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide
23
Restart Procedure
Power application
Set the utility breaker to the ON position.
If your installation includes an XR Battery Enclosure with a DC disconnect switch, set the DC
disconnect switch to the ON position.
disconnect switch to the ON position.
After system boot-up, the display will automatically prompt you on how to confirm/select voltage
and frequency as shown in the following.
and frequency as shown in the following.
WARNING!
Only trained personnel familiar with the construction and the equipment may carry out
the Start-Up procedure.
Only trained personnel familiar with the construction and the equipment may carry out
the Start-Up procedure.
NOTE!
Wait approximately 30 seconds for the system to boot up and carry out self test.
Wait approximately 30 seconds for the system to boot up and carry out self test.
XR Battery Enclosure
Utility
breaker
breaker
UPS