Справочник Пользователя для AEG 1.04

Скачать
Страница из 56
 
 
40 
 
5) Select SETUP,  
 
     6) E.g. if the number of 
    e.g. REDUNDAN and   
         redundant modules is 0, … 
    press 
↵ / Return 
 
 
 
 
 
 
 
 
 
 
The redundancy setup applies after the Setup menu is exited, 
i.e. the UPS displays "Overload" if the power is more than 
8 kVA / 5.6 kW. 
7)  Switch on the PROTECT 1.M in battery mode: 
Having ensured that the batteries are connected correctly, 
switch the battery fuse-switch disconnector to "ON". Then 
press the system switch (located behind the LC display) 
from "OFF" to "ON". The displayed menu is similar to that 
of mains current mode. Now switch on the UPS. The UPS 
switches off if you do not start any action within 
15 seconds; the LC display is switched off after about 
10 minutes: "NO MODULE DETECTED" 
 
Observe the safety precaution! 
For personal safety reasons, do not switch on the 
UPS when the mains is disconnected!  
SETUP REDUNDANCE 
TOTAL  NUM:   3 
Æ
REDUN NUM:   1 
MAX POWER CURRENT 
SETTING: 8kVA/5.6kW 
 
WARNING: 
CURRENT SETTING IS 
NO REDUNDANCY, OK? 
     
YES      Æ NO