Справочник Пользователя для AEG 1.04

Скачать
Страница из 56
 
 
46 
11.4 
Warning Signal if Battery System Not 
Connected,
 
e.g. battery fuse failure 
LED indications 
Warning signal 
LC displays 
Notes 
Operating 
status / 
Operating 
problems
 
 
Norm
al
 
(Normal) 
Battery
 
(On Ba
tter
y) 
Bypa
ss
 
(Fault) 
Fault
 
(Fault) 
 
 
 
Bypass 
mode 
 
 
1 acoustic signal  
every 4 s 
"UPS is not 
connected to 
the battery" 
Check battery 
system;
 
poss. 
fuse fault? 
Normal 
mode 
   
 
1 acoustic signal  
every 4 s 
"UPS is not 
connected to 
the battery" 
Check battery 
system;
 
poss. 
fuse fault? 
 
11.5 
Warning Signal for Phase Loss or Phase 
Sequence Error 
LED indications 
Warning signal 
LC displays 
Notes 
Operating 
status / 
Operating 
problems
 
 
Norm
al
(Normal) 
Battery
(On Ba
tter
y) 
Bypa
ss
(Fault) 
Fault
(Fault) 
 
 
 
Phase loss;
 
Phase 
sequence 
error; bypass 
 
 
 
1 acoustic signal  
every 2 s 
"utility failure 
and sequence 
error" 
No
 
output 
voltage; check 
UPS connection 
Mains failure 
 
normal mode 
 
   
1 acoustic signal  
every 4 s 
"utility failure" 
alarm code 
02 03 09 
Check UPS 
input cabling 
 
Note: 
=  LED lights up 
 
=  LED flashes