Technical Data
Type power
PROTECT C. 1000 (S)
1000 VA (cos 
ϕ
 = 0.7 lag.)
700 W 
PROTECT C. 2000 (S)
2000 VA (cos 
ϕ
 = 0.7 lag.) 
1400 W
PROTECT C. 3000 (S)
3000 VA (cos 
ϕ
 = 0.7 lag.)
2100 W
UPS Input (single phase)
Rated input voltage
220 / 230 / 240 Vac
Voltage tolerance range
160 Vac – 300 Vac ± 5 Vac
Bypass 80 Vac – 264 Vac
Nominal frequency
50 Hz / 60 Hz
(automatic detection)
Frequency tolerance range
± 4 Hz
Current consumption at full load (max.)
PROTECT C. 1000 (S)
7 A
PROTECT C. 2000
10 A
PROTECT C. 2000 S
12 A
PROTECT C. 3000 (S)
16 A
Input power factor
λ
 0.96
Connection
Non-heating appliance 
connector
Datalines
RJ11 (phone, fax, modem)
overvoltage protection
RJ45 (Ethernet 10/100MBit/s)
UPS Output (single phase)
Rated output voltage
220 / 230 / 240 Vac ±2 %
(configuration via software 
“CompuWatch”)
Nominal frequency
50 Hz / 60 Hz ± 0,2 %
(depending on mains)
Voltage waveform
Harmonic distortion
 4 % THD (linear load)
 7 % THD (non-linear load)