Справочник Пользователя для AEG 10000

Скачать
Страница из 58
23 
4.3 Point 
of 
Installation 
Note the following points when setting up the UPS system 
and its external battery units (special accessories): 
♦  The contact surface must be smooth and in level. It must 
also be sufficiently strong and sturdy to avoid vibration 
and shock loads. 
♦  Make sure the mounting is able to support the weight: 
This is particularly important in conjunction with external 
battery units (special accessories). 
♦  Set up the units so that adequate air circulation is 
assured. There must be at least 100 mm clearance at the 
back for ventilation purposes. Do not block the intake 
openings on the front and, if present, on the side of the 
unit. There must be a gap of at least 50 mm here. 
♦  Set up external battery units (special accessories) on the 
side of the UPS system. To ensure the greatest possible 
mechanical stability, you should not set up the external 
battery unit(s) above or below the UPS system. 
♦  Avoid extreme temperatures! We recommend an ambient 
temperature of 15 °C to 25 °C in order to maximise the 
service life of the batteries. Do not expose the units to 
direct sunlight or operate them close to other heat 
sources such as radiators. 
♦  Protect the units against external effects (in particular 
moisture and dust). In this regard, please also refer to the 
instructions in chapter 4.2, page 22 in these operating 
instructions. 
If you transport the unit from a cold room into a warm one, or 
if the room temperature suddenly drops then condensation 
may form inside the unit. To avoid any damage due to 
condensation, leave the unit to acclimatise for 2 hours before 
you switch it on.