Справочник Пользователя для AEG 10000

Скачать
Страница из 58
34 
6 Electrical 
Start-Up 
Verify that UPS voltage of your country corresponds to your 
equipment voltage. The default setting is set to 230 V. Output 
voltage on the UPS system can be adjusted with the software 
“CompuWatch” in steps of 220 Vac, 230 Vac and 240 Vac. 
Turn on the PROTECT C. to the mains 
1. 
Ensure, that the connection have been realised 
according to the installation guide. 
2. 
Ensure, that all loads are switched of. 
3. 
Set manual bypass „Maintenance Switch“ back to 
“UPS” on the rear of the UPS (Pos. 2, page 26). 
Fix the four screws of the cover. 
4. 
Put the prefuse of the low voltage main distributor 
(there, where the UPS system is connected on the 
input side with the mains) back in resp. switch the 
corresponding line fuse on. 
5. 
Activate the mains input circuit breaker (Pos. 3, 
page 26). If necessary switch it to “ON”. 
i
 
Default setting: 
The supply of the loads comes 
via the integrated bypass (Modification of the 
configuration with the provided Software 
„CompuWatch“). Don’t switch on the loads yet. 
6. 
Now switch on the UPS. To do this, press and 
hold the UPS ON switch for about 2 seconds. 
7. 
While powering up, the UPS will perform self-
diagnosis, the Load/Battery level LEDs will be 
turned on and then off one after another in 
ascending order. After synchronising the inverter 
successfully the LED “Inverter” will go on after a 
few seconds, with the UPS in normal mode. If the 
power supply is in order (mains within the range) 
an additionally the LED “Line” will light up.